Pocket Reference

The tables, formulas, and code limits electricians reach for every day — organized by topic.

REFERENCE TOPIC

Motors

Single-phase and three-phase full-load current, plus conductor, disconnect, and protection rules.

Single-phase full-load current

430.248
HP115 V230 V
0.59.84.9
0.7513.86.9
1168
1.52010
22412
33417
55628
7.58040
1010050

Use these table values for conductor, disconnect, and protection sizing rather than the motor nameplate current.

Three-phase full-load current

430.250
HP230 V460 V575 V
0.52.20.90.8
0.753.21.31.1
14.21.71.4
1.562.52
26.83.42.7
39.64.83.9
515.27.66.1
7.522119
10281411
15422117
20542722
25683427
30804032
401045241
501306552
601547762
751929677
10024812499
125312156125
150360180144
200480240192
250604302242

Table values are used for sizing everything in the motor branch circuit. Nameplate current is used only for overload protection where the code says so.

Motor circuit sizing at a glance

ItemRequirementNEC
Branch-circuit conductorsNot less than 125% of the motor FLC430.22
Overload protection, service factor 1.15 or higher125% of nameplate FLC maximum430.32
Overload protection, temp rise 40°C or less125% of nameplate FLC maximum430.32
Overload protection, all other motors115% of nameplate FLC maximum430.32
Branch short-circuit protection, inverse-time breaker250% of FLC maximum430.52
Branch short-circuit protection, dual-element fuse175% of FLC maximum430.52
Branch short-circuit protection, non-time-delay fuse300% of FLC maximum430.52
Motor disconnecting meansAt least 115% of FLC430.110
Several motors on one branch circuit125% of the largest FLC plus 100% of the rest430.24
Combination load (motor plus other load)125% of the largest motor FLC plus the other load430.25

Reminders

  • Short-circuit protection is sized on the table FLC, then rounded up to the next standard size.
  • Overload protection is set from the nameplate current and may be increased once, then again only with documented evidence.
  • The disconnecting means must be within sight of the controller and within sight of the motor for most installations.
  • A motor circuit needs a controller, a disconnect, branch short-circuit protection, and running overload protection — four separate functions.

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.