The tables, formulas, and code limits electricians reach for every day — organized by topic.
REFERENCE TOPIC
Fill percentages, usable raceway area, and conductor areas by size and insulation.
| Conductors in raceway | Maximum fill |
|---|---|
| 1 | 53% |
| 2 | 31% |
| 3 or more | 40% |
| Nipple 24 in or less | 60% |
| Trade size | EMT | RMC | PVC 40 | PVC 80 |
|---|---|---|---|---|
| 1 | 0.346 | 0.396 | 0.333 | 0.238 |
| 2 | 1.409 | 1.586 | 1.255 | 0.960 |
| 3 | 2.731 | 3.008 | 2.424 | 1.919 |
| 4 | 4.738 | 5.021 | 3.855 | 3.074 |
| 5 | — | — | 6.005 | 4.823 |
| 6 | — | — | 8.570 | 6.906 |
| 1/2 | 0.122 | 0.138 | 0.133 | 0.088 |
| 3/4 | 0.210 | 0.239 | 0.197 | 0.134 |
| 1-1/4 | 0.598 | 0.681 | 0.545 | 0.402 |
| 1-1/2 | 0.876 | 0.970 | 0.748 | 0.562 |
| 2-1/2 | 1.904 | 2.122 | 1.670 | 1.297 |
| 3-1/2 | 3.580 | 3.895 | 3.088 | 2.452 |
Square inches available to conductors at the 40% limit. For a single conductor use 53% of the internal area, and for two conductors use 31%.
| Size | THHN / THWN-2 area (sq in) |
|---|---|
| 14 | 0.0097 |
| 12 | 0.0133 |
| 10 | 0.0211 |
| 8 | 0.0366 |
| 6 | 0.0507 |
| 4 | 0.0824 |
| 3 | 0.1043 |
| 2 | 0.1333 |
| 1 | 0.1568 |
| 1/0 | 0.1855 |
| 2/0 | 0.2237 |
| 3/0 | 0.2679 |
| 4/0 | 0.3237 |
| 250 | 0.3970 |
| 300 | 0.4600 |
| 350 | 0.5230 |
| 400 | 0.5860 |
| 500 | 0.7070 |
Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.
Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.