Grounding & Bonding

Grounding electrode and equipment grounding conductor sizing, electrodes, and bonding.

Grounding electrode conductor

250.66
Largest service conductorCopper GECAluminum GEC
2 AWG or smaller86
1/0 through 3/064
Over 3/0 through 350 kcmil42
Over 350 through 600 kcmil21/0
Over 600 through 1100 kcmil1/02/0
Over 1100 kcmil3/04/0

Sized from the largest ungrounded service conductor. A grounding electrode conductor is never required to be larger than 3/0 copper or 4/0 aluminum.

Equipment grounding conductor

250.122
OCPD rating (A)Copper EGCAluminum EGC
151412
201210
30108
40108
60108
10086
20064
30042
40031
50021/0
60012/0
8001/03/0
10002/04/0

Sized from the rating of the overcurrent device protecting the circuit, not from the phase conductors.

Electrode rules

250.52, 250.53
  • A ground rod must be at least 8 ft long and driven to full contact with the soil.
  • A single rod must measure 25 ohms or less. If it does not, install a second rod and no further measurement is required.
  • Bond every available electrode — metal water pipe, structural steel, concrete-encased electrode, ground ring, and rods — into one grounding electrode system.
  • The metal water pipe must be supplemented by another electrode.

Bonding and continuity

  • Bond metal raceways, enclosures, and equipment to the equipment grounding conductor so fault current has a low-impedance path back to the source.
  • Keep the grounded conductor and the equipment grounding conductor separate everywhere downstream of the service or separately derived system.
  • Use listed connectors for grounding and bonding; sheet metal screws are not an acceptable bonding means.
  • Replace any receptacle that will not accept an equipment grounding conductor with a GFCI receptacle marked "no equipment ground."
  • Test continuity of every bonding path before energizing.

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.