Pocket Reference

The tables, formulas, and code limits electricians reach for every day — organized by topic.

REFERENCE TOPIC

Diagrams & Symbols

Offset bend geometry, box fill counting, series and parallel circuits, and schematic symbols.

Conduit bend types

Ten bends cover essentially every run you will make in EMT. Learn the layout for each one and the size of the conduit stops mattering.

90° stub-up

Take a run up a wall into a box, panel, or disconnect.

stub length − take-up90°
  1. Measure from the floor (or the fixed end) to where the back of the bend lands.
  2. Subtract the take-up for the size — 5" on ½" EMT, 6" on ¾", 8" on 1", 11" on 1¼" — and mark that result.
  3. Slide the conduit in until the arrow lines up with the mark, bender on the floor, hook toward you.
  4. Step on the heel and pull through in one steady motion until the handle is vertical.

Back-to-back 90s

Two 90s facing the same way, the span between the backs set by a panel or box spacing.

between backs
  1. Make the first 90 as a stub-up.
  2. For the second bend, measure between the two back-of-bends and subtract the take-up again.
  3. Turn the conduit end for end, line up the second mark on the arrow, and bend.
  4. Keep both bends in the same plane — sight down the run before the second pull.

Offset (two-bend)

Step a run up or down to clear an obstruction, then continue parallel to itself.

risebend 1bend 2
  1. Set the rise and pick the angle: 10°, 22.5°, 30°, 45°, or 60°.
  2. Distance between bends = rise × multiplier (30° × 2.0, 45° × 1.41, 22.5° × 2.61).
  3. Mark both distances from the same reference end, and add the shrink back before you cut.
  4. Bend the first mark, turn the conduit 180° in the bender, bend the second to the same angle.
  5. Set it on the floor — the two legs must come out parallel and in one plane.

Four-point saddle

Hop over a pipe, coupling, or beam with equal legs on both sides of the obstruction.

obstruction45° legs
  1. Mark the center of the obstruction on the conduit.
  2. Using 45° outer bends, mark each side at saddle depth × 2.5, then mark the center line.
  3. Bend both outside marks 45° in the same direction.
  4. Turn the bender and bend the center mark 22.5° the opposite way.
  5. Set it over the obstruction and confirm both legs sit flat on the surface.

Three-point saddle

A quick V over a single round obstruction where a wide saddle is not needed.

center bend 45°22.5° legs
  1. Mark the center of the obstruction.
  2. Mark each side at depth × 2.5 for 45° bends, the same layout as a four-point.
  3. Bend the center mark 45° first, then both outside marks 22.5° the opposite direction.
  4. Test it against the pipe it has to clear before you cut the conduit.

Kick 90

A 90 that also has to move sideways to line up with an offset box or panel entry.

set in the wall plane90° riser
  1. Bend the 90 first and hold it against the wall or layout.
  2. Mark where the riser has to move over and pick a small kick angle — 22.5° or 30° handles most.
  3. Put the arrow on the kick mark with the bender rotated so the kick moves in the right direction.
  4. Sight down the riser: the kick sits in the wall plane and must not twist the 90 out of plumb.

Parallel offsets

A rack of conduits that step together and stay evenly spaced.

equal spacing, same angle
  1. Bend the first conduit as the pattern and check it against the layout.
  2. For each following conduit, move the first mark by conduit spacing × multiplier of the angle.
  3. Bend every conduit to the same angle and in the same plane as the pattern.
  4. Strap the rack and confirm the spacing at both ends of the offset.

Angle bend

Turn a run by a fixed angle — 30°, 45°, 60° — without a second bend.

θfixed angle, one bend
  1. Mark the point of the angle and set the arrow on it.
  2. Pull the angle in one motion and check it with a protractor against the bender's marks.
  3. Above 45°, allow for springback: pull a degree or two past and let the conduit relax.

Concentric bends

Several 90s sharing one center, nested inside each other into a panel or gutter.

one shared center
  1. Establish one common center point on the wall, panel, or gutter.
  2. Give each conduit a larger radius than the last; add at least one conduit diameter plus the spacing between bends so they never touch.
  3. Every size has its own take-up, so mark each conduit against its own number and the shared center.
  4. Bend from the inside out, checking each sweep against the one already installed.

Segment (multi-shot) bend

A large-radius sweep too big for a one-shot pull, bent in equal increments.

equal incrementslarge sweep
  1. Divide the total angle into equal segments — 4° to 10° per pull is typical.
  2. Mark the segments along the developed arc so the sweep is shared evenly.
  3. Pull each mark the same small increment, sliding to the next mark each time.
  4. Check the finished sweep against a string line or template before installing.

Every bend below is bent on the same bender — what changes is the layout: where the marks go, which bender mark they sit on, and which direction each pull faces.

Bending by EMT size

358.24

Take-up changes with trade size and bender, so the stub mark is measured length minus take-up. Match the bender to the size before you mark anything.

EMT trade sizeBenderTake-up (deduct)90° stub markField note
½"Hand bender5"length − 5"One-shot 90s; the size most offsets and saddles are laid out on.
¾"Hand bender6"length − 6"Same technique as ½", a longer handle pull.
1"Hand bender or mechanical8"length − 8"Two hands on the handle; keep the heel planted.
1¼"Mechanical or hydraulic11"length − 11"Check the shoe chart — most hand benders stop at 1".
1½"Mechanical or hydraulic14"length − 14"Support the run while the shoe comes up to angle.
2"Mechanical or hydraulic16"length − 16"Sweep 90s if the radius allows; otherwise segment-bend.

Take-up belongs to the bender, not the conduit. Confirm the number stamped on your bender or its chart before the first mark of a job — a wrong take-up is a wrong stub every time.

BENDER MARKS

  • Arrow — Primary mark on most hand benders — line it up for stub-ups and angle bends.
  • Star — Back-of-bend reference — used for offsets, saddles, and back-to-back layouts.
  • Rim notch — Center-line reference on the shoe — used to center saddles on an obstruction.

How to bend conduit in the field

358.24 · 358.30

The same ten steps work on a service rack, a classroom bender, or a panel change in a basement.

  1. 1

    Lay out the whole run first

    Measure the complete path — every obstruction, box entry, and turn — before anything is cut. Bends are easy; guesswork is not recoverable.

  2. 2

    Add the shrink before you cut

    Every offset shortens the run by rise × shrink. Add it back into the measured length so the last bend still lands on the box.

  3. 3

    Cut long, trim after

    You can always cut a stub shorter. There is no way to stretch one that came up 2 inches short.

  4. 4

    Mark on the bender side

    Mark with a pencil or marker on the same face of the conduit that meets the bender's arrow, so the mark stays visible while you load it.

  5. 5

    Match bender to size

    Every shoe is built for one trade size and wall type. Never force a conduit into the wrong bender — it crushes the wall and kinks at the elbow.

  6. 6

    Load with the seam on the inside

    The weld seam rides on the inside of the bend or the neutral axis. On the outside it stretches, splits, and snags the pull.

  7. 7

    One steady pull

    Heel planted on the floor, both hands on the handle, one continuous motion. Stopping mid-bend and restarting leaves a flat spot in the sweep.

  8. 8

    Check, then correct for springback

    Square, level, or protractor against the bend. Steel springs back a degree or two, so above 45° pull slightly past the mark and let it relax.

  9. 9

    Dry-fit before installing

    Bends in the wrong plane cannot be undone without cutting. Lay the assembly out on the floor against the layout and check every plane.

  10. 10

    Support it like straight conduit

    Secured within 3 ft of every box and every 10 ft on the run (358.30) — a bend is not a support.

WHAT GOES WRONG

  • Bending across a coupling or fitting shoulder — the conduit kinks there and the pull fails.
  • Re-bending a 90 to "fix" it — the elbow flattens and the conductors will not pass.
  • Forgetting shrink — the run ends up short at the last box.
  • Twisting the conduit between bends — the offset comes out dog-legged and out of plane.
  • Exceeding 360° of bend between pull points, offsets included (358.26).
  • Marking with the arrow instead of the star on an offset — both bends end up off by the take-up.

Support and bend limits: no more than 360° of bend between pull points (358.26), supported within 3 ft of every box and every 10 ft on the run (358.30).

Offset bend geometry

358.24

Lay out an offset with three numbers: the rise, the multiplier for the angle, and the shrink.

θDistance between bendsRiseBend 1Bend 2
  • Distance between bends = rise × multiplier for the angle you choose.
  • 10°: 5.76 multiplier — 22.5°: 2.61 — 30°: 2.00 — 45°: 1.41 — 60°: 1.15.
  • Total bend between pull points may not exceed 360°, offsets included.
  • Add the shrink back into the run before you cut, or the stub comes up short.
Bend angleMultiplierShrink per inch of riseWhere it is used
10°5.76 (round to 6.0)1/16"Long, shallow step over a minor obstruction.
22.5°2.613/16"Half of a 45° saddle; tight quarters.
30°2.001/4"The everyday offset — easy to pull, easy to check.
45°1.413/8"Short offset, and the outer bends of a four-point saddle.
60°1.151/2"Only where space forces it — watch the 360° total.

Box fill in one picture

314.16

Every item in the box gets a volume allowance. Add them, compare to the box volume, done.

4 conductors, No. 124 × 2.25 = 9.001 cable clamp2.251 device yoke2 × 2.25 = 4.50All grounds, one count2.254 in. square × 1-1/2 in. deep — 21.0 in³Total 18.00 in³ — passes
  • Each conductor that terminates or splices inside the box counts once; conductors passing straight through do not.
  • Devices count twice the largest conductor connected to them.
  • Cable clamps, connectors, and support fittings each add one allowance.
  • All equipment grounding conductors together count as one, based on the largest one present.

Series and parallel circuits

L1L2L3SERIESOne path — same current everywhereL1L2L3PARALLELSame voltage across every load
  • Series: one path, same current through every load, voltages add up to the source.
  • Parallel: every load sees the full source voltage, currents add up to the supply current.
  • Branch circuits and receptacles are wired in parallel — one failed lamp never kills the rest of the circuit.
  • Never wire loads in series on a branch circuit; the voltage divides and the loads underperform.

Schematic symbols

SymbolMeaningWhere it shows up
─o─Single-pole switchControls one load from one location
─o=o─Three-way switchControls one load from two locations
─o×o─Four-way switchBetween two three-ways for three or more locations
⌾Duplex receptacleGeneral-purpose outlet
◍GFCI receptacleWet, outdoor, and kitchen locations
⌽LuminaireLighting outlet
⏚GroundEquipment grounding conductor termination
⊣⊢CapacitorMotor starting and power factor correction
MMotorAny motor-driven load
TTransformerVoltage change, separately derived systems

Drawn conventions used on plans and ladder diagrams, not a code requirement.

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.