The tables, formulas, and code limits electricians reach for every day — organized by topic.
REFERENCE TOPIC
Insulation types and ratings, ambient correction, bundling adjustment, and standard sizes.
| Type | Temperature rating | Typical use | Watch for |
|---|---|---|---|
| THHN | 90°C dry, 75°C wet | Branch circuits and feeders in raceways, gutters, and cable trays | The workhorse branch-circuit conductor |
| THWN-2 | 90°C dry and wet | Raceways indoors, outdoors, and underground | Preferred where the raceway can get wet |
| XHHW-2 | 90°C dry and wet | Feeders, services, and large branch circuits | Smaller outside diameter than THHN in large sizes |
| NM-B | 90°C conductors, 60°C ampacity | Concealed dry locations in dwellings | Ampacity is taken from the 60°C column (334.80) |
| UF | 90°C dry, 60°C wet | Direct burial, underground feeders, outbuildings | Rated for direct burial; sunlight-resistant where marked |
| SE / SER | 75°C or 90°C | Service entrance conductors and panel feeders | Read the marking — rating drives the ampacity column |
| MC / AC | 90°C conductors, 75°C terminations | Exposed or concealed feeders and branch circuits | Needs listed connectors and anti-short bushings |
| Ambient | 60°C | 75°C | 90°C |
|---|---|---|---|
| 21–25°C (70–77°F) | 1.08 | 1.05 | 1.04 |
| 26–30°C (78–86°F) | 1.00 | 1.00 | 1.00 |
| 31–35°C (87–95°F) | 0.91 | 0.94 | 0.96 |
| 36–40°C (96–104°F) | 0.82 | 0.88 | 0.91 |
| 41–45°C (105–113°F) | 0.71 | 0.82 | 0.87 |
| 46–50°C (114–122°F) | 0.61 | 0.75 | 0.82 |
| 51–55°C (123–131°F) | 0.50 | 0.67 | 0.76 |
| 56–60°C (132–140°F) | 0.42 | 0.58 | 0.71 |
| 61–65°C (141–149°F) | 0.35 | 0.52 | 0.65 |
| 66–70°C (150–158°F) | 0.30 | 0.45 | 0.58 |
| 71–75°C (159–167°F) | 0.26 | 0.39 | 0.50 |
| 76–80°C (168–176°F) | 0.20 | 0.33 | 0.43 |
Multiply the table ampacity by the factor for the ambient temperature the conductor sees. The 30°C columns are the table basis.
| Conductors in raceway or cable | Adjustment factor |
|---|---|
| 4–6 | 0.80 |
| 7–9 | 0.70 |
| 10–20 | 0.50 |
| 21–30 | 0.45 |
| 31–40 | 0.40 |
| 41 and up | 0.35 |
Applies when more than three current-carrying conductors share a raceway or cable. Apply both this and the ambient correction, then compare to the overcurrent device.
Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.
Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.