Pocket Reference

The tables, formulas, and code limits electricians reach for every day — organized by topic.

REFERENCE TOPIC

Conductors & Cables

Insulation types and ratings, ambient correction, bundling adjustment, and standard sizes.

Conductor and cable types

Article 310, 334, 338, 330
TypeTemperature ratingTypical useWatch for
THHN90°C dry, 75°C wetBranch circuits and feeders in raceways, gutters, and cable traysThe workhorse branch-circuit conductor
THWN-290°C dry and wetRaceways indoors, outdoors, and undergroundPreferred where the raceway can get wet
XHHW-290°C dry and wetFeeders, services, and large branch circuitsSmaller outside diameter than THHN in large sizes
NM-B90°C conductors, 60°C ampacityConcealed dry locations in dwellingsAmpacity is taken from the 60°C column (334.80)
UF90°C dry, 60°C wetDirect burial, underground feeders, outbuildingsRated for direct burial; sunlight-resistant where marked
SE / SER75°C or 90°CService entrance conductors and panel feedersRead the marking — rating drives the ampacity column
MC / AC90°C conductors, 75°C terminationsExposed or concealed feeders and branch circuitsNeeds listed connectors and anti-short bushings

Ambient temperature correction

310.15(B)(1)
Ambient60°C75°C90°C
21–25°C (70–77°F)1.081.051.04
26–30°C (78–86°F)1.001.001.00
31–35°C (87–95°F)0.910.940.96
36–40°C (96–104°F)0.820.880.91
41–45°C (105–113°F)0.710.820.87
46–50°C (114–122°F)0.610.750.82
51–55°C (123–131°F)0.500.670.76
56–60°C (132–140°F)0.420.580.71
61–65°C (141–149°F)0.350.520.65
66–70°C (150–158°F)0.300.450.58
71–75°C (159–167°F)0.260.390.50
76–80°C (168–176°F)0.200.330.43

Multiply the table ampacity by the factor for the ambient temperature the conductor sees. The 30°C columns are the table basis.

Adjustment for bundled conductors

310.15(C)(1)
Conductors in raceway or cableAdjustment factor
4–60.80
7–90.70
10–200.50
21–300.45
31–400.40
41 and up0.35

Applies when more than three current-carrying conductors share a raceway or cable. Apply both this and the ambient correction, then compare to the overcurrent device.

Standard overcurrent device ratings

240.6(A)
15 A20 A25 A30 A35 A40 A45 A50 A60 A70 A80 A90 A100 A110 A125 A150 A175 A200 A225 A250 A300 A350 A400 A450 A500 A600 A700 A800 A1000 A1200 A1600 A2000 A2500 A3000 A4000 A5000 A6000 A

Standard conductor sizes (AWG and kcmil)

1412108643211/02/03/04/02503003504005006007501000

Ampacity ground rules

  • Terminations limit the usable ampacity column: 60°C for most small conductors, 75°C for listed 75°C terminations (110.14(C)).
  • Size branch circuits at 125% of a continuous load, then protect at the next standard size (210.19(A), 210.20(A)).
  • The next-size-up rule lets you round up to the next standard breaker only when the conductor ampacity is at least the load and the next size does not exceed the conductor ampacity (240.4(B)).
  • Small conductors are capped regardless of ampacity: No. 14 at 15 A, No. 12 at 20 A, No. 10 at 30 A (240.4(D)).
  • NM cable ampacity is taken at 60°C even though the conductors are rated 90°C (334.80).
  • Never exceed the lowest temperature rating anywhere in the circuit — conductor, termination, or device.

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.