Pocket Reference

The tables, formulas, and code limits electricians reach for every day — organized by topic.

REFERENCE TOPIC

Box Fill

Conductor volume allowances, box-mounted items, counting rules, and standard box volumes.

Volume allowance per conductor

314.16(B)(1)
ConductorVolume allowance (cu in)
6 AWG5.00
8 AWG3.00
10 AWG2.50
12 AWG2.25
14 AWG2.00
16 AWG1.75
18 AWG1.50

Based on the largest conductor in the box. Conductors 18 through 6 AWG use the allowance per conductor; larger conductors use the volume marked on the box or the engineered tables.

What counts toward fill

314.16(B)
Box-mounted itemVolume allowance
Device (switch/receptacle)2× largest wire
Internal Cable Clamp1× largest wire
Fixture Stud / Hickey1× largest wire
Equipment Grounding Conductor1× largest EGC
Isolated Ground Receptacle+1× largest EGC

Counting rules

  • Each conductor that originates outside the box and terminates or is spliced inside counts once.
  • Conductors that pass through without splicing or terminating are not counted.
  • All equipment grounding conductors together count as one conductor, based on the largest one.
  • A device yoke counts as two conductors of the largest size connected to it.
  • Each internal cable clamp, fixture stud, or hickey counts as one conductor of the largest size.
  • A box containing only a switch or receptacle must still hold the device allowance plus every conductor.

Common box volumes

BoxVolume (cu in)
Single-Gang Device × 2-1/4" Deep3.0
Single-Gang Device × 2-1/2" Deep3.5
Single-Gang Device × 3" Deep4.0
3" Octagon × 1-1/2" Deep7.5
Two-Gang Masonry × 2-1/4" Deep7.5
4" Octagon × 1-1/4" Deep12.5
FS Single-Gang × 1-1/2" Deep13.0
4" Octagon × 1-1/2" Deep15.5
4" Square × 1-1/4" Deep18.0
4" Square × 1-1/2" Deep21.0
4" Octagon × 2-1/8" Deep21.5
4-11/16" Square × 1-1/4" Deep25.5
4-11/16" Square × 1-1/2" Deep29.5
4" Square × 2-1/8" Deep30.3
4-11/16" Square × 2-1/8" Deep42.0

Always use the volume marked on the box when one is marked. Cast boxes, FS boxes, and boxes over 100 cu in have separate allowances.

Worked example

A box holds five 12 AWG conductors, two 14 AWG conductors, one internal clamp, one receptacle, and one 12 AWG equipment grounding conductor.

  • 5 × 2.25 = 11.25 cu in
  • 2 × 2.00 = 4.00 cu in
  • clamp = 2.25 cu in
  • device = 2 × 2.25 = 4.50 cu in
  • EGC = 2.25 cu in
  • Total = 24.25 cu in, so the box must be marked at least 24.25 cu in

Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.

Run the full NEC calculator

Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.