The tables, formulas, and code limits electricians reach for every day — organized by topic.
REFERENCE TOPIC
Conductor volume allowances, box-mounted items, counting rules, and standard box volumes.
| Conductor | Volume allowance (cu in) |
|---|---|
| 6 AWG | 5.00 |
| 8 AWG | 3.00 |
| 10 AWG | 2.50 |
| 12 AWG | 2.25 |
| 14 AWG | 2.00 |
| 16 AWG | 1.75 |
| 18 AWG | 1.50 |
Based on the largest conductor in the box. Conductors 18 through 6 AWG use the allowance per conductor; larger conductors use the volume marked on the box or the engineered tables.
| Box-mounted item | Volume allowance |
|---|---|
| Device (switch/receptacle) | 2× largest wire |
| Internal Cable Clamp | 1× largest wire |
| Fixture Stud / Hickey | 1× largest wire |
| Equipment Grounding Conductor | 1× largest EGC |
| Isolated Ground Receptacle | +1× largest EGC |
| Box | Volume (cu in) |
|---|---|
| Single-Gang Device × 2-1/4" Deep | 3.0 |
| Single-Gang Device × 2-1/2" Deep | 3.5 |
| Single-Gang Device × 3" Deep | 4.0 |
| 3" Octagon × 1-1/2" Deep | 7.5 |
| Two-Gang Masonry × 2-1/4" Deep | 7.5 |
| 4" Octagon × 1-1/4" Deep | 12.5 |
| FS Single-Gang × 1-1/2" Deep | 13.0 |
| 4" Octagon × 1-1/2" Deep | 15.5 |
| 4" Square × 1-1/4" Deep | 18.0 |
| 4" Square × 1-1/2" Deep | 21.0 |
| 4" Octagon × 2-1/8" Deep | 21.5 |
| 4-11/16" Square × 1-1/4" Deep | 25.5 |
| 4-11/16" Square × 1-1/2" Deep | 29.5 |
| 4" Square × 2-1/8" Deep | 30.3 |
| 4-11/16" Square × 2-1/8" Deep | 42.0 |
Always use the volume marked on the box when one is marked. Cast boxes, FS boxes, and boxes over 100 cu in have separate allowances.
A box holds five 12 AWG conductors, two 14 AWG conductors, one internal clamp, one receptacle, and one 12 AWG equipment grounding conductor.
Reference only. Verify every value against the code edition adopted in your jurisdiction and the manufacturer's listing before installing.
Electrical Safety Compass is a supplemental study aid and field reference tool only. It is designed to help prepare apprentices for their licensing exams and to assist working electricians in the field. It does not replace any required classroom instruction, formal apprenticeship coursework, or supervised on-the-job training mandated by your state, licensing board, or apprenticeship program. Always complete all legally required education and supervised hours before performing electrical work.